⚠ CO₂ DISCHARGE IN PROGRESS — EVACUATE PROTECTED SPACE — DO NOT ENTER ⚠
SYSTEM CONTROL
Zone Select
Operating Mode

Discharge Control

Boundary Dampers
D-01 OPEN
D-02 OPEN
D-03 OPEN
D-04 OPEN
D-05 OPEN
D-06 OPEN
CO₂ SYSTEM SCHEMATIC — P&ID
SYSTEM STATUS & ALARMS
0.04%
v/v   Design: 40%

System Pressure57.4 bar
Cylinders Charged72
Cylinders Dischrg0
VentilationRUNNING
Dampers Closed0/6
Delay Counter--
W System awaiting scenario --:--
EVACUATION CHECKLIST
All items must be completed before CO₂ release is authorised.
Personnel count confirmed — all clear of protected space
Pre-alarm horn sounded — minimum 20 seconds
All ventilation fans stopped
All 6 boundary dampers confirmed CLOSED
Fuel oil quick-closing valves confirmed shut
Bridge / duty officer notified
CO₂ room door confirmed accessible for abort
0/7 items complete — discharge LOCKED
EVENT LOG
-- CO₂ system log initialised --
SYSTEM PARAMETERS
Cylinder Pressure57.4bar
Reserve Pressure56.8bar
CO₂ Concentration0.04% v/v
Cylinders Remaining72/ 72

Protected Space: Engine Room
Required Qty: 1,680 kg (37 cyl)
Design Conc: 40% v/v (34% min)
Release Time: ≤ 2 min (85%)
Cylinder Mass: 45 kg CO₂ each
Cylinder Press: 55–60 bar @ 21°C
CO₂ SYSTEM — FULL P&ID SCHEMATIC
LINE IDENTIFICATION
MAIN HEADER
MH-001 Main CO₂ HeaderCHARGED
MH-002 Pilot LineARMED
MH-003 Release ManifoldSTANDBY
ZONE VALVES
ZV-ER Engine RoomOPEN
ZV-CPR Cargo Pump RoomCLOSED
PRESSURE INDICATORS
PI-001 System Header57.4 bar
PI-002 Reserve Bank56.8 bar
PI-003 ER Nozzle Inlet0.0 bar
PI-004 CPR Nozzle Inlet0.0 bar
CO₂ BOTTLE ROOM — CYLINDER BANK OVERVIEW
CYLINDER STATUS
MAIN BANK — 72 CYLINDERS
Cylinders Charged72 / 72
Cylinders Discharged0
Bank Pressure (avg)57.4 bar
Temperature21°C
RESERVE BANK — 18 CYLINDERS
Reserve Charged18 / 18
Reserve Pressure56.8 bar
Isolation ValveCLOSED
LOW PRESSURE ALARMS
Warning Level52 bar
Alarm Level48 bar
LP Switch StatusHEALTHY
INSPECTION
Last Weighing2025-01 DOC
Next Due2027-01
Hydro Test Due2030-01
CO₂ DISTRIBUTION PIPEWORK — NOZZLE LAYOUT
NOZZLE & PIPE DATA
ENGINE ROOM — 24 NOZZLES
Upper Zone Nozzles8 × 6mm
Lower Zone Nozzles10 × 8mm
Bilge Nozzles6 × 6mm
Coverage Volume3,850 m³
CARGO PUMP ROOM — 8 NOZZLES
Upper Nozzles4 × 5mm
Lower Nozzles4 × 5mm
Coverage Volume820 m³
PIPE SCHEDULE
Main HeaderDN100 Sch.40
Zone BranchDN65 Sch.40
DistributionDN40 Sch.40
Nozzle DropDN20 Sch.80
PILOT CYLINDER SYSTEM — ACTUATION CONTROL
PILOT CYLINDER STATUS
PILOT CYLINDERS (2 OFF)
Pilot Cyl. No.1ARMED
Pilot Cyl. No.2 (backup)ARMED
Pilot Pressure59.1 bar
ACTUATION MODES
Auto ReleaseENABLED
Manual Pull BoxCO₂ ROOM
Remote ReleaseBRIDGE
SOLENOID VALVES
SOL-01 Auto ReleaseDE-ENERGISED
SOL-02 Pilot ActuationDE-ENERGISED
PULL-BOX STATUS
Pull-Box No.1 (CO₂ Rm)SEALED
Pull-Box No.2 (Deck)SEALED
FIRE DETECTION — ENGINE ROOM & PUMP ROOM
DETECTOR STATUS
ENGINE ROOM — SMOKE DETECTORS
SD-ER-01 Upper FwdNORMAL
SD-ER-02 Upper AftNORMAL
SD-ER-03 Mid LevelNORMAL
SD-ER-04 Lower FwdNORMAL
SD-ER-05 Lower AftNORMAL
ENGINE ROOM — HEAT DETECTORS
HD-ER-01 Purifier AreaNORMAL
HD-ER-02 Booster PumpNORMAL
HD-ER-03 IncineratorNORMAL
CARGO PUMP ROOM
SD-CPR-01 UpperNORMAL
SD-CPR-02 LowerNORMAL
HD-CPR-01 Pump AreaNORMAL
DETECTION PANEL
FDAS Loop 1HEALTHY
FDAS Loop 2HEALTHY
Battery Backup30 hr CHARGED
VENTILATION & BOUNDARY DAMPER SYSTEM
VENTILATION CONTROLS
SUPPLY FANS
SF-01 ER Main SupplyRUNNING
SF-02 ER Aux SupplyRUNNING
SF-03 CPR SupplyRUNNING
EXHAUST FANS
EF-01 ER Main ExhaustRUNNING
EF-02 ER Aux ExhaustRUNNING
EF-03 CPR ExhaustRUNNING
BOUNDARY DAMPERS (6 OFF)
D-01 ER Upper FwdOPEN
D-02 ER Upper MidOPEN
D-03 ER Upper AftOPEN
D-04 ER Lower FwdOPEN
D-05 ER Lower AftOPEN
D-06 CPR DamperOPEN

ZONE SELECTOR VALVE ARRANGEMENT
ZONE SELECTOR CONTROLS
ZONE SELECTOR BLOCK
Selected ZoneENGINE ROOM
Selector PositionER
ZONE VALVES
ZV-ER StatusOPEN
ZV-CPR StatusCLOSED
Interlock ActiveYES
SELECT ZONE
Per FSS Code Ch.5 §4.1 — zone selector valve must be positioned before discharge. Only one zone can be selected at a time.
DISCHARGE SEQUENCE — STEP-BY-STEP PROCEDURE
STEP 1 — PRE-ALARM
1Activate pre-alarm — audible/visual warning throughout protected space. Minimum 20 seconds per SOLAS.
Confirm all personnel have evacuated protected space.
STEP 2 — VENTILATION STOP
2Stop all supply and exhaust ventilation fans serving the protected space.
Confirm fan stopped status on VFD / MCC panel.
STEP 3 — DAMPER CLOSURE
3Close all 6 boundary dampers — confirm closed indication on each.
Confirm 6/6 dampers closed on status panel.
STEP 4 — 20-SECOND DELAY
420-second abort window begins. Abort available until counter expires.
Delay counter: --
STEP 5 — CO₂ RELEASE
5CO₂ pilot cylinders actuated — zone valve opens — main bank discharges.
CO₂ concentration: 0.04% v/v
SEQUENCE CONTROLS

SEQUENCE STATUS
SYSTEM READY — SELECT ZONE AND INITIATE
PRE-DISCHARGE SAFETY CHECKLIST
All items must be completed and confirmed before CO₂ discharge is authorised. Per FSS Code Ch.5 and SMS Fire Fighting Plan.
PERSONNEL SAFETY
All personnel accounted for — protected space clear
SOLAS II-2/Reg.17.4 · FSS Code Ch.5 §3
Personnel on boundary watch assigned
SMS Fire Fighting Plan §7.2
SCBA sets confirmed available for re-entry team
FSS Code Ch.5 §3.1.4
SPACE ISOLATION
Pre-alarm sounded — minimum 20-second evacuation warning
SOLAS II-2/Reg.10.7.1 · FSS Code Ch.5 §4.3
All ventilation fans stopped and confirmed
FSS Code Ch.5 §4.2 — fans must stop before release
All 6 boundary dampers confirmed CLOSED — visual check
FSS Code Ch.5 §4.2 — dampers confirmed by indicator lights
All access doors to protected space closed and clipped
FSS Code Ch.5 §4.2.3
MACHINERY ISOLATION
Fuel oil quick-closing valves confirmed shut
SOLAS II-2/Reg.17 — fuel isolation before CO₂ release
Main engine and generators stopped if safe to do so
FSS Code Ch.5 §3.4 — CO₂ is non-conducting, safe for live equipment
Emergency power source confirmed available (EDG)
SOLAS II-1/Reg.43 — emergency power during flooding
NOTIFICATIONS
Bridge / Officer of the Watch notified
SMS Fire Fighting Plan §4.1
CO₂ room door accessible — abort pull-box unobstructed
FSS Code Ch.5 §4.3.3 — abort available during 20s delay
0/12 items confirmed — discharge LOCKED
REGULATORY REFERENCE
SOLAS REQUIREMENTS
II-2/Reg.10 — Fire-extinguishing systems
II-2/Reg.17 — Fuel isolation before flooding
II-2/Reg.19 — Crew training requirements
FSS CODE
Ch.5 §3 — System design requirements
Ch.5 §4 — Operating procedures
Ch.5 §4.2 — Ventilation and dampers
Ch.5 §4.3 — Discharge sequence
IACS UR F15
Cylinder quantity calculation
Pipe sizing and nozzle design
Low-pressure alarm requirement
Annual inspection and weighing
CO₂ HAZARD DATA
IDLH: 40,000 ppm (4% v/v)
Extinguishing conc: 34% v/v min
Design conc: 40% v/v
Re-entry: SCBA mandatory