HV exit exam questions and answers — Set 13 — High Voltage Safety Officer & Switchgear Operations
Set 13 of the High Voltage Safety Officer & Switchgear Operations (HV) exit exam bank — 30 of 428 questions, with the correct option marked and a one-line explanation for every one. Read it end to end, jump to a single set, or search it — then sit the same bank as a timed paper. The real DG Shipping exit exam is 30 marks with 15 to pass.
These are the bank's original groupings. Practising deals the whole bank out again every time you reshuffle, so a practice “Set 3” is a different 30 questions each time — the set numbers below are the source file's, and are only used here so the key stays navigable. Options are listed in their original order with fixed letters; when you practise, those move too.
Bank last rebuilt .
30 of 30 shown · Set 13
Nothing in this set matches that. Try a shorter word, or search the whole key.
Set 13 — 30 HV exit exam questions with answers
1. The maximum output frequency of a cycloconverter is practically limited to approximately:
- A. Twice the supply frequency
- B. One third to about 40% of the supply frequency
- C. Ten times the supply frequency
- D. Exactly the supply frequency
2. In a synchroconverter (load commutated inverter, LCI) drive, the inverter thyristors are commutated mainly by:
- A. Forced commutation from IGBTs
- B. The ship's emergency battery
- C. The back-EMF of the synchronous motor
- D. A large DC link capacitor
3. A pulse-width modulated (PWM) voltage source inverter drive is characterised by:
- A. No rectifier stage
- B. Direct AC-AC conversion
- C. A DC link capacitor and fast switching devices such as IGBTs in the inverter
- D. A DC link inductor and naturally commutated thyristors
4. A current source inverter (CSI) drive is identified by:
- A. A large DC link capacitor
- B. A large DC link inductor that keeps the DC link current nearly constant
- C. Use of a cycloconverter
- D. No DC link at all
5. Why is the voltage-to-frequency (V/f) ratio kept approximately constant when controlling the speed of an induction motor with a frequency converter?
- A. To allow the motor to run without a supply
- B. To increase slip to 100%
- C. To keep the motor current at zero
- D. To maintain constant magnetic flux in the motor so it can develop rated torque without saturating
6. Field-oriented (vector) control of an induction motor drive works by:
- A. Switching the motor between star and delta
- B. Varying only the voltage while frequency is fixed
- C. Separately controlling the flux-producing and torque-producing components of stator current
- D. Inserting resistance in the rotor circuit
7. Direct torque control (DTC) in a motor drive differs from conventional PWM vector control because it:
- A. Controls motor torque and flux directly via hysteresis comparators and a switching table, without a separate modulator
- B. Uses a mechanical gearbox
- C. Requires a DC motor
- D. Controls only the motor voltage magnitude
8. The synchronous speed of a 6-pole induction motor supplied at 60 Hz is:
- A. 1,800 rpm
- B. 900 rpm
- C. 1,200 rpm
- D. 3,600 rpm
9. Large HV motors such as bow thrusters are often started by auto-transformer, soft starter or frequency converter rather than direct-on-line mainly to:
- A. Reverse the motor direction
- B. Increase the starting current
- C. Reduce the motor's rated power
- D. Limit the large starting current and the resulting voltage dip on the switchboard
10. Energising a large HV/LV transformer can cause a magnetising inrush current several times rated current. Transformer differential protection avoids tripping on this by:
- A. Increasing the system frequency
- B. Harmonic (second harmonic) restraint
- C. Earthing the transformer neutral solidly
- D. Removing the CTs during energisation
11. HV/LV distribution transformers on board ships are most commonly of which type?
- A. Oil-filled transformers with conservator tanks
- B. Dry-type (cast resin or air-insulated) transformers
- C. Auto-transformers without isolation
- D. Rotating transformers
12. Before working inside a variable frequency drive cabinet after isolation, why must the specified waiting time be observed?
- A. The DC link capacitors may retain a dangerous charge for several minutes
- B. The fans must cool down
- C. The PMS needs to reset
- D. The cabinet door interlock opens only after an hour
13. Large HV synchronous motors and generators on board are usually excited by a brushless system in which:
- A. Carbon brushes feed DC from batteries directly to the rotor
- B. Permanent magnets alone provide excitation, which cannot be adjusted
- C. The stator is fed with DC
- D. An AC exciter and rotating diode rectifier on the shaft supply DC to the main field
14. Running an HV switchboard with the bus tie breaker open (split bus) during critical operations is done mainly to:
- A. Reduce the number of generators needed
- B. Prevent a single fault from blacking out the entire power plant
- C. Increase fault level on each section
- D. Allow closing generators without synchronising
15. When a VSI drive decelerates a motor with high inertia, energy flows back into the DC link. If there is no regenerative front end, this energy is commonly dissipated by:
- A. The AVR
- B. The motor anti-condensation heater
- C. A braking chopper and braking resistor
- D. Opening the main breaker
16. HV motor stator coils are normally insulated using form-wound coils impregnated by:
- A. Paraffin wax
- B. Simple varnish dipping without vacuum
- C. Vacuum pressure impregnation (VPI) with resin
- D. Paper wrapped with no impregnation
17. A synchronous motor that is over-excited operates at:
- A. Zero speed
- B. Leading power factor, supplying reactive power to the system
- C. Lagging power factor, drawing reactive power
- D. Speed above synchronous speed
18. How is the vacuum integrity of a vacuum circuit breaker interrupter usually checked during maintenance?
- A. By listening for gas leaks
- B. By weighing the bottle
- C. By applying a specified high test voltage across the open contacts and checking that no breakdown occurs
- D. By measuring the contact resistance only
19. Contact erosion in a vacuum circuit breaker cannot be seen directly. It is usually assessed by:
- A. Measuring the insulation resistance of the control circuit
- B. Opening the vacuum bottle
- C. Counting the number of shutters
- D. Checking the contact wear indicator or gap measurement on the moving contact mechanism against manufacturer's limits
20. Main contact resistance of an HV circuit breaker is measured using:
- A. A micro-ohmmeter injecting a high DC current through the closed contacts
- B. A clamp meter
- C. An analogue multimeter on the ohms range
- D. An insulation resistance tester at 5 kV
21. A withdrawable HV circuit breaker is in the 'test' position when:
- A. It is fully connected to the busbar and closed
- B. Its earthing switch is closed and the breaker is closed on load
- C. Its main contacts are disconnected from the busbar and cable, but the auxiliary/control circuits are connected so its operation can be tested
- D. It is removed from the switchboard
22. Racking an HV circuit breaker in or out is mechanically prevented unless:
- A. The busbar earthing switch is closed
- B. The cable is energised
- C. The control supply is switched off
- D. The breaker is in the open position
23. Thermographic (infrared) surveys of HV switchboards are carried out to detect:
- A. Vacuum loss in VCBs
- B. Overheating connections and components while the equipment is on load
- C. Earth faults on de-energised cables
- D. Insulation resistance values
24. An earth fault alarm appears on an HV system with high-resistance neutral earthing. The first step in remedial action is to:
- A. Ignore the alarm until the next port
- B. Remove the neutral earthing resistor
- C. Identify the faulty feeder using earth fault relay indications and the switching plan, then isolate it in a controlled manner
- D. Immediately open all generator breakers
25. When isolating an HV feeder using a withdrawable circuit breaker with an integral earthing switch, the correct sequence is:
- A. Rack out the closed breaker, then open it
- B. Open the breaker, rack it to isolated position and lock the shutters, prove dead, then close the earthing switch
- C. Prove dead after closing the earthing switch only
- D. Close the earthing switch, then open the breaker
26. Before closing an HV earthing switch on a circuit, it is essential to prove it dead because:
- A. Closing an earth onto a live circuit causes a severe short circuit and arc flash
- B. Earthing switches are only rated for live closing
- C. The earthing switch will not close otherwise
- D. The PMS requires it
27. An SF6 circuit breaker gives a 'low gas density' alarm followed by a lockout. The purpose of the lockout is to:
- A. Increase the gas pressure automatically
- B. Bypass the protection relays
- C. Prevent the breaker from operating when it cannot interrupt current safely
- D. Allow the breaker to operate faster
28. When opening an SF6 circuit breaker compartment that has interrupted faults, personnel should use PPE and ventilation because:
- A. Arced SF6 decomposes into toxic and corrosive by-products and powders
- B. Pure SF6 is explosive
- C. SF6 is radioactive
- D. SF6 is lighter than air and causes frostbite
29. During routine maintenance of HV switchgear, insulating surfaces such as bushings and spouts should be:
- A. Greased heavily with ordinary grease
- B. Cleaned with lint-free cloth and approved cleaner, and inspected for tracking marks
- C. Sprayed with water
- D. Painted with conductive paint
30. On an HV circuit breaker with a spring-operated mechanism, the closing spring is normally:
- A. Not used; the breaker closes by gravity
- B. Charged only by the protection relay
- C. Charged by the arc energy
- D. Charged by a motor and released to close the breaker, which in turn charges the opening spring